material: RUBBER
tipology: MULTICORE

H07RN-F ECA

Rubber cables

Flexible red copper
    certificates

Applications
Appliances Cables

Conditions of employment
Use in industrial and agricultural workshops, building sites, for heavy duty applications and supplying industrial and agricultural machines and appliances where cables are subject to medium mechanical stresses (e.g. heating plates, inspection lamps, electric tools such as drills, circular saws, and domestic electric tools) use in dry, humid or moist rooms; fixed installations e.g. on rough-cast in temporary buildings and huts for accommodation purposes.

Type of electrical conductor
Flexible red copper

Main rule
EN 50525-2-21

Conductor
EN 60228; IEC 60228

Self-extinguishing
EN 60332-1-2; IEC 60332-1-2

Oil resistance
EN 60811-404; IEC 60811-404


Description

Flexible single and multicore power cables, rubber insulated, under heavy polychloroprene sheath or other equivalent elastomer sheath.

More informations




Technical Specifications:   Download

Review number n. 0 - 23/2/2018
Nominal tension 450/750 V
Type of insulation EI4
Type of outer sheath EM2
Color of the outer sheath Black
Operating temperature -25° C | +60° C
Short circuit temperature 200° C on the conductor (max 5 sec.)
Test voltage 2500 V
Cable marking ELETTRO BRESCIA IEMMEQU <HAR> H07RN-F
Minimum radius of curvature If the outer diameter of the cable is between 8 and 12 mm: 4 times the max. outer diameter in case of non-constrained motion, and 3 times in case of fixed installation. If the outer diameter is greater than 12 mm: 5 times the max. outer diameter in case of non- constrained motion and 4 times in case of fixed instalIation.


Insulation identification
number of cores Insulation identification sequence
3 Yellow/Green-Blue-Brown
2 Blue-Brown
4 Yellow/Green-Blue-Brown-Black / Yellow/Green-Brown-Black-Grey
5 Yellow/Green-Blue-Brown-Black-Grey


Sections
Nominal section Max wire diameter Conductor diameter Insulation thickness Average sheath thickness Minimum external diameter Maximum external diameter Copper electric resistance 20°C Indicative weight CU Factor
(Nxmm2) (mm) (mm) (mm) (mm) (mm) (mm) (Ω/km) (kg/km) (kg/km)
2x1,00 0,21 1,215 0,80 1,30 7,7 10,0 19,50 115 19,2
2x1,50 0,26 1,435 0,80 1,50 8,5 11,0 13,30 140 28,8
2x2,50 0,26 1,879 0,90 1,70 10,2 13,1 7,98 200 48
2x4,00 0,31 2,445 1,00 1,80 11,8 15,1 4,95 275 76,8
2x6,00 0,31 2,955 1,00 2,00 13,1 16,8 3,30 365 115,2
3G1,00 0,21 1,215 0,80 1,40 8,3 10,7 19,50 135 28,8
3G1,50 0,26 1,435 0,80 1,60 9,2 11,9 13,30 170 43,2
3G2,50 0,26 1,879 0,90 1,80 10,9 14,0 7,98 240 72
3G4,00 0,31 2,445 1,00 1,90 12,7 16,2 4,95 335 115,2
3G6,00 0,31 2,955 1,00 2,10 14,1 18,0 3,30 445 172,8
4G1,00 0,21 1,215 0,80 1,50 9,2 11,9 19,50 165 38,4
4G1,50 0,26 1,435 0,80 1,70 10,2 13,1 13,30 205 57,6
4G2,50 0,26 1,879 0,90 1,90 12,1 15,5 7,98 290 96
4G4,00 0,31 2,445 1,00 2,00 14,0 17,9 4,95 420 153,6
4G6,00 0,31 2,955 1,00 2,30 15,7 20,0 3,30 565 230,4
5G1,00 0,21 1,215 0,80 1,60 10,2 13,1 19,50 205 48
5G1,50 0,26 1,435 0,80 1,80 11,2 14,4 13,30 255 72
5G2,50 0,26 1,879 0,90 2,00 13,3 17,0 7,98 360 120
5G4,00 0,31 2,445 1,00 2,20 15,6 19,9 4,95 520 192
5G6,00 0,31 2,955 1,00 2,50 17,5 22,2 3,30 695 288


The manufacturer reserves the right to modify all or part of the data shown in this catalog