H1Z2Z2-K
Solar cables
Flexible tinned copper-
certificates
-
Photovoltaic Cables
Conditions of employment
The single core H1Z2Z2-K cable represents a right solution to link the solar cellars between them or to wire with frequency converters and terminal boards. The H1Z2Z2-K cable guarantees good resistance to UV-rays and various weather conditions. The wide working temperature range allows the use also in extreme conditions, avoiding deterioration caused by heat and permitting a right use of the fotovoltaic panel in every season.
Type of electrical conductor
Flexible tinned copper
Main rule
EN 50618
Conductor
EN 60228; IEC 60228
Self-extinguishing
EN 60332-1-2; IEC 60332-1-2
Ozone resistance
EN 50396 8.1.3
Description
The single core H1Z2Z2-K cable represents a right solution to link the solar cellars between them or to wire with frequency converters and terminal boards. The H1Z2Z2-K cable guarantees good resistance to UV-rays and various weather conditions. The wide working temperature range allows the use also in extreme conditions, avoiding deterioration caused by heat and permitting a right use of the fotovoltaic panel in every season.
Type of electrical conductor
Flexible tinned copper
Main rule
EN 50618
Conductor
EN 60228; IEC 60228
Self-extinguishing
EN 60332-1-2; IEC 60332-1-2
Ozone resistance
EN 50396 8.1.3
Description
Low smoke halogen-free, flexible, single-core power cables with cross-linked insulation and sheath.
More informations
Review number | n. 3 - 18/2/2019 |
Nominal tension | 1,0/1,0 kVca - 1,5 kVdc |
Type of insulation | Compound conforming to EN 50618 |
Type of outer sheath | Compound conforming to EN 50618 |
Color of the outer sheath | Black, blue, red |
Operating temperature | -40° C | +90° C |
Short circuit temperature | Max 250° C 5 sec |
Test voltage | 6500 Vac - 15000 Vdc |
Cable marking | ELETTRO BRESCIA H1Z2Z2-K (I/II)* 1xsect. mm² TÜV Rheinland Reg. Nr. R (60109330/60108022)* Dca-s2,d2,a1 max 1,8KVdc |
Minimum radius of curvature | 4 times the cable diameter for fixed and mobile laying. |
Sections
The manufacturer reserves the right to modify all or part of the data shown in this catalogNominal section | Max wire diameter | Conductor diameter | Insulation thickness | Average sheath thickness | Average diameter | Copper electric resistance 20°C | Indicative weight | CU Factor |
(Nxmm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (kg/km) | (kg/km) |
1x2,50 | 0,25 | 0,000 | 0,75 | 0,80 | 5.1 | 8,21 | 47 | 24 |
1x4,00 | 0,30 | 0,000 | 0,72 | 0,80 | 5.4 | 5,09 | 58 | 38,4 |
1x6,00 | 0,30 | 0,000 | 0,74 | 0,80 | 6.0 | 3,39 | 78 | 57,6 |
1x10,00 | 0,40 | 0,000 | 0,73 | 0,80 | 7.0 | 1,95 | 125 | 96 |
1x16,00 | 0,40 | 0,000 | 0,74 | 0,90 | 8.2 | 1,24 | 184 | 153,6 |