SILICONE GS (TINNED COPPER)
Silicone cables
Flexible tinned copper-
certificates
-
Appliances Cables
Conditions of employment
For high temperatures produced by engines, transformers, generators, electric equipment, wiring harnesses for household appliances and lighting purposes.
Type of electrical conductor
Flexible tinned copper
Main rule
Conductor
EN 60228; IEC 60228
Description
For high temperatures produced by engines, transformers, generators, electric equipment, wiring harnesses for household appliances and lighting purposes.
Type of electrical conductor
Flexible tinned copper
Main rule
Conductor
EN 60228; IEC 60228
Description
Flexible single core cable with silicone rubber insulation.
More informations
Review number | n. 7 - 10/1/2018 |
Nominal tension | 300/500 V |
Type of insulation | Silicone rubber |
Color of the outer sheath | On demand (one or two colours) |
Operating temperature | -60° C | +180° C |
Short circuit temperature | 230° C (max 5 sec.) |
Test voltage | 2000 V |
Cable marking | No markings on cable |
Insulation tolerance | ± 0,1 |
Sheath tolerance | ± 0,1 |
Sections
The manufacturer reserves the right to modify all or part of the data shown in this catalogNominal section | Max wire diameter | Conductor diameter | Insulation thickness | Average sheath thickness | Average diameter ± 0,1 | Copper electric resistance 20°C | Indicative weight | CU Factor |
(Nxmm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (kg/km) | (kg/km) |
1x0,50 | 0,21 | 0,000 | 0,60 | NA | 2.05 | 40,10 | 9,5 | 4,8 |
1x0,75 | 0,21 | 0,000 | 0,60 | NA | 2.35 | 26,70 | 12,5 | 7,2 |
1x1,00 | 0,21 | 0,000 | 0,60 | NA | 2.45 | 20,00 | 14,8 | 9,6 |
1x1,50 | 0,26 | 0,000 | 0,60 | NA | 2.75 | 13,70 | 20,1 | 14,4 |
1x2,50 | 0,26 | 0,000 | 0,70 | NA | 3.35 | 8,21 | 30,7 | 24 |
1x4,00 | 0,31 | 0,000 | 0,80 | NA | 4.15 | 5,09 | 48 | 38,4 |
1x6,00 | 0,31 | 0,000 | 0,80 | NA | 4.70 | 3,39 | 64,7 | 57,6 |