material: PVC
tipology: SINGLECORE

H07V-U

PVC cables

Solid red copper
    certificates

Applications
Appliances Cables

Conditions of employment
Installation in surface-mounted or embedded conduits, or similar closed systems.

Type of electrical conductor
Solid red copper

Main rule
EN 50525-2-31

Conductor
EN 60228; IEC 60228

Self-extinguishing
EN 60332-1-2; IEC 60332-1-2


Description

Single core non-sheathed cables with rigid conductor.

More informations





Review number n. 5 - 22/4/2015
Nominal tension 450/750 V
Type of insulation TI1
Color of the outer sheath On demand (one or two colours)
Operating temperature +5° C | +70° C (55° C in environments with fire hazard)
Short circuit temperature 160° C on the conductor max 5 seconds (140° C in environments with fire hazard)
Test voltage 2500 V
Cable marking ELETTRO BRESCIA IEMMEQU <HAR> H07V-U
Minimum radius of curvature 6 times the max outer diameter.
Insulation tolerance ± 0,1
Sheath tolerance ± 0,2


Sections
Nominal section Max wire diameter Conductor diameter Insulation thickness Average sheath thickness Minimum external diameter Maximum external diameter Copper electric resistance 20°C Indicative weight CU Factor
(Nxmm2) (mm) (mm) (mm) (mm) (mm) (mm) (Ω/km) (kg/km) (kg/km)
1x1,50 1,35 1,35 0,70 NA 2,6 3,2 12,10 20 14,4
1x2,50 1,75 1,75 0,80 NA 3,2 3,9 7,41 30 24
1x4,00 2,25 2,25 0,80 NA 3,6 4,4 4,61 55 38,4
1x6,00 2,80 2,80 0,80 NA 4,1 5,0 3,01 81 57,6


The manufacturer reserves the right to modify all or part of the data shown in this catalog

share: