Solid red copper-
certificates
-
Appliances Cables
Conditions of employment
Installation in surface-mounted or embedded conduits, or similar closed systems and where the maximum conductor temperature in normal use of 90 °C. is not exceeded. If installed in distribution systems the maximum continuous operating temperature shall be limited to 70 °C.
Type of electrical conductor
Solid red copper
Main rule
EN 50525-2-31
Conductor
EN 60228; IEC 60228
Self-extinguishing
EN 60332-1-2; IEC 60332-1-2
Description
Installation in surface-mounted or embedded conduits, or similar closed systems and where the maximum conductor temperature in normal use of 90 °C. is not exceeded. If installed in distribution systems the maximum continuous operating temperature shall be limited to 70 °C.
Type of electrical conductor
Solid red copper
Main rule
EN 50525-2-31
Conductor
EN 60228; IEC 60228
Self-extinguishing
EN 60332-1-2; IEC 60332-1-2
Description
Single core non-sheathed cables for internal wiring.
More informations
Review number | n. 5 - 22/4/2015 |
Nominal tension | 450/750 V |
Type of insulation | TI3 |
Color of the outer sheath | On demand (one or two colours) |
Operating temperature | +5° C | +90° C |
Short circuit temperature | 160° C on the conductor (max 5 sec.) |
Test voltage | 2500 V |
Cable marking | ELETTRO BRESCIA IEMMEQU <HAR> H07V2-U |
Minimum radius of curvature | 6 times the diameter of cable. |
Insulation tolerance | ± 0,1 |
Sheath tolerance | ± 0,2 |
Sections
The manufacturer reserves the right to modify all or part of the data shown in this catalogNominal section | Max wire diameter | Conductor diameter | Insulation thickness | Average sheath thickness | Minimum external diameter | Maximum external diameter | Copper electric resistance 20°C | Indicative weight | CU Factor |
(Nxmm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (kg/km) | (kg/km) |
1x1,50 | 1,35 | 1,35 | 0,70 | NA | 2,6 | 3,2 | 12,10 | 20 | 14,4 |
1x2,50 | 1,75 | 1,75 | 0,80 | NA | 3,2 | 3,9 | 7,41 | 30 | 24 |