LEV 160 HALOGEN FREE
Rubber cables
Flexible tinned copper-
certificates
-
Electromechanics Cables
Conditions of employment
Cable produced with a low-halogenic compound and high oxigen index and, therefore, against flame propagation. With an exellent mechanical varnishes and oil resistance it is also used in the electric motors, in the transformers, in the condenser, in the household electrical appliances, in the lamps, in the resistors and in some particulars of the cars. Used in electric motors.
Type of electrical conductor
Flexible tinned copper
Main rule
Conductor
EN 60228; IEC 60228
Self-extinguishing
EN 60332-1-2; IEC 60332-1-2
Description
Cable produced with a low-halogenic compound and high oxigen index and, therefore, against flame propagation. With an exellent mechanical varnishes and oil resistance it is also used in the electric motors, in the transformers, in the condenser, in the household electrical appliances, in the lamps, in the resistors and in some particulars of the cars. Used in electric motors.
Type of electrical conductor
Flexible tinned copper
Main rule
Conductor
EN 60228; IEC 60228
Self-extinguishing
EN 60332-1-2; IEC 60332-1-2
Description
Flexible, single-core, rubber insulated sheath cables, based on vinyl acetate, for indoor networks. Compound with a vinyl acetate base, suitable for the insulation of conductors having no sheath. Low halogenic content rubber, with high oxygen index. No-flame propagation cable, excellent mechanical and oil resistance.
More informations
Review number | n. 6 - 27/11/2017 |
Nominal tension | 300/500 V sect. 0,35-1,00 450/750 V sect. > 1,5 |
Type of insulation | G19 |
Insulation breakage load | = 9 N/mm² |
Insulation elongation | = 150% |
Color of the outer sheath | On demand (one or two colours) |
Operating temperature | -40° C | +160° C (not continuos) |
Short circuit temperature | 200° C on the conductor (max 5 sec.) |
Test voltage | 2000 V |
Cable marking | ELETTRO BRESCIA (section) mm² LEV 160 HALOGEN FREE |
Minimum radius of curvature | 6 times the max outer diameter. |
Insulation tolerance | ± 0,1 |
Sheath tolerance | ± 0,1 |
Sections
The manufacturer reserves the right to modify all or part of the data shown in this catalogNominal section | Max wire diameter | Conductor diameter | Insulation thickness | Average sheath thickness | Average diameter ± 0,1 | Copper electric resistance 20°C | Indicative weight | CU Factor |
(Nxmm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (kg/km) | (kg/km) |
1x0,50 | 0,21 | 0,859 | 0,60 | NA | 2.1 | 40,10 | 8,8 | 4,8 |
1x0,75 | 0,21 | 1,052 | 0,70 | NA | 2.4 | 26,70 | 12,1 | 7,2 |
1x1,00 | 0,21 | 1,215 | 0,70 | NA | 2.5 | 20,00 | 14,4 | 9,6 |
1x1,50 | 0,26 | 1,485 | 0,70 | NA | 2.8 | 13,70 | 19 | 14,4 |
1x2,50 | 0,26 | 1,918 | 0,70 | NA | 3.4 | 8,21 | 30,2 | 24 |
1x4,00 | 0,31 | 2,445 | 0,80 | NA | 4.2 | 5,09 | 47,2 | 38,4 |
1x6,00 | 0,31 | 2,955 | 0,80 | NA | 4.8 | 3,39 | 65,6 | 57,6 |