Rubber single and multicore cables for low-voltage
Multicore, flexibile power cables, rubber insulated, under mean rubber sheath.
Rated voltage Uo/U 300/500 V.
CEI 20-19 CENELEC HD 22
Nominal section
Max. diameter of the conductor wires
Insulator mean thickness
Sheath mean thickness
Outer diameter min.
Outer diameter max.
Cable approximate weight
Max. eletrical resistance at 20° C
n° x mm²
mm
mm
mm
mm
mm
Kg/Km
Ohm/Km
2x0,75
0,21
0,6
0,8
5,7
7,4
58
26,7
2x1
0,21
0,6
0,9
6,1
8
69
20,0
2x1,5
0,26
0,8
1,0
7,6
9,8
100
13,7
2x2,5
0,26
0,9
1,1
9
11,5
145
8,21
3G0,75
0,21
0,6
0,9
6,2
8,1
72
26,7
3G1
0,21
0,6
0,9
6,5
8,5
83
20,0
3G1,5
0,26
0,8
1,0
8
10,4
125
13,7
3G2,5
0,26
0,9
1,1
9,6
12,4
175
8,21
3G4
0,31
1
1,2
11,3
14,5
217
5,09
3G6
0,31
1
1,4
12,8
16,3
283
3,39
4G0,75
0,21
0,6
0,9
6,8
8,8
90
26,7
4G1
0,21
0,6
0,9
7,1
9,3
100
20,0
4G1,5
0,26
0,8
1,1
9
11,6
150
13,7
4G2,5
0,26
0,9
1,2
10,7
13,8
220
8,21
4G4
0,31
1
1,3
12,7
16,2
271
5,09
4G6
0,31
1
1,5
14,2
18,1
375
3,39
5G0,75
0,21
0,6
1,0
7,6
9,9
105
26,7
5G1
0,21
0,6
1,0
8
10,3
120
20,0
5G1,5
0,26
0,8
1,1
9,8
12,7
180
13,7
5G2,5
0,26
0,9
1,3
11,9
15,3
260
8,21
Allowable currents for rubber insulated cables:
Nominal section of conductor
Allowable current
With rubber insulation
mm²
Unipolar
Triple-pole
0,75
6
6
1
10
10
1,5
16
16
2,5
25
20
4
32
25
6
40
-
Remarks: These values apply in most cases. Further information are to be sought for the unusual cases, e. g.:
1 if the room temperatures are too high, that is to say above 30° C.
2 for very long cables.
3 in presence of poor ventilation.
4 when the cables are used for the others purposes, for ex. inner wiring harness of a device.
Applications:
for general use in domestic rooms, in the kitchen, offices and for power supply of portable devices which are subject to slight mechanical stresses (for ex. aspirators, kitchen, utensils, welding, irons, toasters). It is not suitable for: permanent use outdoors, farming, farm or industrial workshops or for power supply of non domestic tools.
Conductor:
single copper wire, annealed, not tinned.
Insulation:
EI 4 rubber.
Sheath:
EM 3 rubber.
Marking:
continuous marking:
ELETTROBRESCIA IEMMEQU <HAR> H05RR-F
on the sheath and/or on the insulating material.
Max. operating temperature:
60° C on the conductor.
Max. temperature in case of short circuit:
(max. duration 5 sec.): 200° C on the conductor.
Min. bending radius:
if the outer diameter of the cable is between 6 and 12 mm: 4 times the max. outer diameter in case of non-constrained motion, and 3 times in case of fixed installation. If the outer diameter is greater than 12 mm: 5 times the max. outer diameter in case of non constrained motion and 4 times in case of fixed installation.
Max. laying stress:
15 N for mm² of copper total section.
Core colours:
bipolar blue-brown
triple-pole yellow/green-blue-brown
Four-pole yellow/green-brown-black-grey
or
yellow/green-blue-brown-black
Five-pole yellow/green-blue-brown-black-grey
Sheath colour:
standard = black.
Other colours can be supplied upon request and for quantities to be agreed.
N.B.: the cable can be supplied upon request also without ground conductor.
 